Operating Room No. | Room Area (m2) | Room Volume (m3) | HEPA Air Flow (m3/hr) | Air Exchange Rate (times/hr) | Fresh Air Volume (m3/hr) |
---|---|---|---|---|---|
1 | 48.3 | 144.9 | 4,680 | 32.3 | 250 |
3 | 63.4 | 190.2 | 5,760 | 30.2 | 1,000 |
5 | 47.5 | 142.5 | 4,680 | 32.8 | 750 |
6 | 53.0 | 159.0 | 4,4680 | 30.0 | 750 |
7 | 62.0 | 186.0 | 5,760 | 30.1 | 1,000 |
11 | 48.3 | 144.9 | 4,680 | 32.2 | 750 |
12 | 48.0 | 144.0 | 4,680 | 32.5 | 750 |
13 | 47.9 | 143.7 | 4,680 | 32.5 | 750 |
14A | 75.9 | 227.7 | 8,160 | 35.8 | 1,200 |
15 | 47.6 | 142.8 | 4,680 | 32.7 | 750 |
17 | 40.7 | 112.1 | 4,680 | 38.3 | 700 |
18 | 40.9 | 122.7 | 4,680 | 38.1 | 550 |